Building Wires and Cables >>>
 
 
 
THW : 750 V PVC INSULATED, SINGLE CORE.
   
CONDUCTOR : Solid and stranded annealed copper,
  Size 0.5 mm2 up to 500 mm2
INSULATION : PVC-Any colour.
CLASSIFICATION : Maximum conductor temperature C.
  Circuit voltage not exceeding 750 volts.
TESTING VOLTAGE : 2,500 volts.
REFERENCE : TIS 11-2531, Table 4
 
   
THW, MEA TYPE A
   
TIS 11-2531
   
TABLE 4
   
Nominal
Number
Insulation
Max.
Minimum
Maximum
Cable
Standard
cross
and
thickness
overall
insulation
continuous
weight
length
sectional
diameter
diameter
resistance at
current rating
(approx.)
area
of wire
in free air
(mm2)
(No./mm)
(mm)
(mm)
(Ampere)
(kg/km)
(m)
0.5
1/0.80
0.8
3.0
0.0175
9
11
100/C
1
1/1.13
0.8
3.3
0.0141
13
17
100/C
1
7/0.43
0.8
3.5
0.0135
13
18
100/C
1.5
1/1.38
0.8
3.6
0.0123
17
22
100/C
1.5
7/0.53
0.8
3.8
0.0116
17
24
100/C
2.5
1/1.78
0.8
4.0
0.0102
23
32
100/C
2.5
7/0.67
0.8
4.3
0.0093
23
35
100/C
4
1/2.25
0.9
4.8
0.0094
32
49
100/C
4
7/0.85
0.9
5.2
0.0085
32
50
100/C
6
7/1.04
0.9
5.8
0.0073
43
75
100/C
10
7/1.35
1.1
7.2
0.0069
60
120
100/C
16
7/1.70
1.1
8.4
0.0057
83
180
100/C
25
7/2.14
1.3
10.5
0.0054
114
280
100/C
35
19/1.53
1.3
11.5
0.0047
141
380
100/C
50
19/1.78
1.5
13.5
0.0046
175
500
500/D
70
19/2.14
1.5
15.5
0.0039
221
700
500/D
95
19/2.52
1.7
18.0
0.0038
275
1,000
500/D
120
37/2.03
1.7
19.5
0.0034
321
1,200
500/D
150
37/2.25
1.9
21.5
0.0034
367
1,500
500/D
185
37/2.52
2.1
24.0
0.0034
424
1,900
500/D
240
61/2.25
2.3
27.0
0.0033
505
2,500
500/D
300
61/2.52
2.5
30.0
0.0032
581
3,100
500/D
400
61/2.85
2.7
33.5
0.0030
675
3,900
500/D
500
61/3.20
3.1
38.5
0.0031
781
5,000
500/D
C : Packing in coil.
D : Packing in drum.
     
Copyright © 2004 . All rights reserved. Powered by Readyhost2u
TECK SOON SENG ELECTRIC CO.,LTD.
664 Samyek, Charoenkrung Road, Sampuntawong, Bangkok 10100 Thailand.
Tel.(662) 2244946, 2227896, 2214261 Fax.(662) 2257635
E-mail Address : [email protected]